Electrical Characteristics
|
Nominal Insulation Voltage Ui
|
250V (phase-to-ground) / /500 V (phase-to-phase) |
Maximum working voltage UBmax - 1P, 1P+N,
|
240/415 VAC |
Maximum working voltage UBmax - 2P, 3P, 3P+N, 4P
|
415 VAC |
Rated short-circuit capacity icn (IEC/EN60898)
|
6kA |
Rated impulse withstand voltage Uimp (1.2/50)
|
4kv |
Dielectric test voltage
|
2kV (50/60Hz, (1min) |
Over-voltage category
|
II |
Isolation function
|
Available |
Pollution Class
|
2 |
Electric shock protection grade
|
II |
Trip type
|
Thermal magnetic trip |
Thermal magnetic trip characteristics
|
Type C curve (5In-10In) - |
Electrical and mechanical accessories
|
- |
Mechanical Characteristics
|
Handle
|
Black, pad printing indicating ON-OFF position |
Mechanical endurance
|
Cycle Times 25,000 |
Electrical endurance
|
Cycle Times 6,000 |
Protection grade
|
Installed in distribution box IP40 / Installed directly IP20 |
Mechanical shock resistance
|
30g, 3 shocks, lasting 11ms (No significant vibration or shock) |
Anti-vibration (IEC/EN 60947-2)
|
No significant vibration or shock |
Rated ambient temperature
|
30°C |
Operating ambient temperature (daily mean temperature)
|
-20°C-+60°C |
Storage temperature
|
-40°C-+70°C |
Installation Features
|
Terminal form
|
U terminal |
Maximum wiring capacity
|
Current ratings 1-63A; 25mm² |
Maximum ultimate torque
|
Current ratings 1-63A; 3N.m |
Tool
|
Crosshead screwdriver or flathead screwdriver |
Installation
|
Installed on standard DIN gude rail (35mm) |
Wiring Type
|
Top or bottom |